Performance Comparison of a Buck Converter using PID Control and Fuzzy Logic Control Under Varying Load Characteristic

27 Nov

Authors: Rosa Citrasari, Associate Professor Triwahju Hardianto, Associate Professor Bambang Sri Kaloko, Professor Bambang Sujanarko, RB Moch Gozali

Abstract: A buck converter, the type of controller used significantly affects the stability of the output voltage when the system is operated under varying load characteristics. MATLAB/Simulink was selected to support the research process, which will focus on comparing the performance of PID control with fuzzy logic control under three load characteristics: resistive (R), resistive-inductive (R), and resistive-capacitive (RC). The input voltage used in the system is 12 volts, while the reference voltage is 5 volts. The rise time, settling time, overshoot, and steady-state error parameters are used to evaluate the performance of a buck converter. Simulation results show that the output voltage of both methods falls within the range of 4.997-5.003 V, with a steady-state error of 0-0.06%. Fuzzy control has a faster rise time (0.007-0.015 s) and lower overshoot (1.5-5.8%) compared to PID, while PID has a shorter settling time (0.001-0.002 s) compared to fuzzy control (0.009-0.011 s). These results indicate that fuzzy logic control is superior at accelerating the initial response and reducing overshoot, whereas PID control is superior at accelerating the time to reach steady-state conditions. Thus, a comparison of the performance of the two methods shows that the selection of a controller must take into account the transient response characteristics and the accuracy of the output voltage for each load variation.